|
|
 |
MIL-STD-2036: General Requirements for Electronic Equipment Specifications |
 |  |
| |
5.1.1.1 Alternating Current (ac)
Power
Equipment shall be suitable for installation under the
conditions specified for type I electrical power in MIL-STD-1399, section 300
and the additional requirements specified herein. Electrical tests shall be as
specified in MIL-STD-1399, section 300 and Appendix D.
5.1.1.1.1 Additional requirements. The duration for the emergency line
voltage conditions of plus 35 percent specified in MIL-STD-1399, section 300
shall be changed from "2 minutes to indefinitely". The emergency condition of
minus 100 percent (frequency or voltage) will be treated as a power
interruption. Momentary power interruptions will be limited in duration to 100
milliseconds. Short term power interruptions will be limited in duration to 5
minutes.
5.1.1.1.2 Fully hardened. Equipment shall remain fully operational through
the conditions specified for 440 Volt (V), type I power in accordance with
MIL-STD-1399, section 300 and as modified by 5.1.1.1.1; equipment shall remain
operational through momentary power interruptions, and rapidly (within 1
second) restart following short term power interruptions.
5.1.1.1.3 Minimal acceptance. Equipment shall be fully operational within
the normal tolerance limits specified for type I power in MIL-STD-1399,
section 300. The preferred equipment service is 440 V, 60 Hz then 115 V, 60
Hz. Equipment may shutdown or go into a standby condition, but not be damaged,
when operating outside these limits.
5.1.1.1.4 Ruggedization techniques. The ship's electrical power system is
significantly different from commercial standards. For example, fault current
of public utilities will typically be limited to 65,000 Amperes (A) at 13,000
V, where shipboard fault current is limited to 100,000 A at 450 V (with two of
three generators paralleled). With proper care, COTS equipment can be
ruggedized to be powered from the ship's electrical service. The primary
considerations for ruggedization are as follows:
(a). MIL-STD-1399,
section 300 specifies a harmonic current limit of 3 percent of the fundamental
for equipment rated 1 kilovolt-ampere (kVA) or more. The typical approach has
been to get a waiver, which is unsatisfactory.The shipboard electrical system
has a lower reactance/resistance ratio than the commercial world, and harmonic
currents have a higher impact on voltage distortion. Studies that have been
performed by Naval Sea Systems Command (NAVSEA) indicate that harmonic current
limits should be lowered below present standards.
(b). The voltage
variations specified in MIL-STD-1399, section 300 are more severe than those
in the commercial environment. The peak value may be as high as 220 V for up
to 2 minutes for 115 V equipment. This may be sufficient to damage commercial
equipment. Voltage spikes are particularly severe, specified at 1000 V for 115
Vac equipment where commercial equipment is typically rated for
600V.
(c). The line and return leads on the 115-V, 60-Hz service are
both "hot", that is, both line and return spade connectors on convenience
outlets have a potential to the ground, and the ground (safety) spade
connector is grounded to the ship's hull. Commercial equipment will connect
the return lead to ground at a power panel, and the return lead on commercial
equipment may not be fully insulated. If the return lead is not disconnected
when the equipment is shut-off, the equipment will remain energized presenting
a safety hazard when assumed to be shut-off.
(d). Equipment which is
permanently located and is energized more than 50 percent of the working day,
such as copiers, personal computers and peripherals, soda machines, and money
machines, are not to be connected to the ship's isolated receptacle circuits.
Convenience outlet services are rated 15A, and present a fire hazard when
overloaded. Equipment of this type are to be connected to a separate
dedicated, hard wired circuit supplied by the lighting distribution
system.
(e). To ruggedize for the forgoing conditions, equipment may
adopt the approach indicated in Appendix A. In effect, a power conditioner is
placed between the equipment and the electrical system. Since harmonic
currents are minimized, such types of power conditioners are referred to as
"unity power factor power supplies". Navy Standard Power Supplies do not meet
the 3 percent current harmonic limits in accordance with MIL-STD-1399, section
300. Appendix A recommends a polyphase transformer since transformer
technologies are mature, and transformers are both reliable and robust. Solid
state unity power factor power supplies are being developed; however, the
specifier should be aware that this technology is not mature and the risk of
failing to meet specified performance and reliability criteria is
greater.
(f). An alternative for 115-V equipment rated at less than 1
kVA is to use a double-pole switch to disconnect both power and return lines.
The equipment shall be tested to verify that the equipment return is fully
insulated from the equipment case. Voltage arrestors shall be applied to
protect against voltage spikes; voltage arrestors that conduct at less than
220V shall be removed and replaced with voltage arrestors of a higher rating.
The equipment shall be tested for operation at plus 35 percent voltage, or
over voltage protection applied to remove the equipment from the line under
such conditions.
(g). An Electrical Power Interface Compatibility
(EPIC) mobile test facility is available for testing equipment under the
electrical power conditions specified in MIL-STD-1399, section 300. Further
information on this facility may be obtained from NAVSEA, Code 56Z14.
|
 |
|
|
| |
| |